[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937050":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937050,605,1,"单选题","对报警阀组及附件安装时不正确的有（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","干式报警阀、预作用报警阀安装在温度不低于4℃的室内，防止冰冻",false,{"key":16,"text":17,"correct":14},"B","干式报警阀、预作用报警阀充气连接管接口在报警阀气室充注水位以上部位，且充气连接管的直径不应小于15mm；止回阀、截止阀安装在充气连接管上",{"key":19,"text":20,"correct":14},"C","干式报警阀、预作用报警阀安装完成后，向报警阀气室注入高度为50~100mm的清水以封闭阀瓣",{"key":22,"text":23,"correct":24},"D","安全排气阀安装报警阀后平时充气管路总干管上",true,"参考《自动喷水灭火系统施工及验收规范》5.3.5：“雨淋阀组的安装应符合下列要求：2.预作用系统雨淋阀组后的管道若需充气，其安装应按干式报警阀组有关要求进行”，参考《自动喷水灭火系统施工及验收规范》5.3.4：“干式报警阀组的安装应符合下列要求：1.应安装在不发生冰冻的场所。故A正确；2.安装完成后，应向报警阀气室注入高度为50~100㎜的清水。故C正确；3.充气连接管接口应在报警阀气室充注水位以上部位，且充气连接管的直径不应小于15毫米；止回阀、截止阀应安装在充气连接管上。故B正确；5.安全排气阀应安装在起源与报警之间，且应靠近报警阀，故D错误；",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]