[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937048":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937048,605,1,"单选题","消防系统中，干式消火栓系统的充水时间不应大于（ ）min，干式自动喷水灭火系统的配水管道充水时间，不宜大于（ ）min；预作用系统与雨淋系统的配水管道充水时间，不宜大于（ ） min。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10，1，2",false,{"key":16,"text":17,"correct":14},"B","10，2，1",{"key":19,"text":20,"correct":21},"C","5，1，2",true,{"key":23,"text":24,"correct":14},"D","5，2，1","参考《消规》7.1.6：“干式消火栓系统的充水时间不应大于5min，并应符合相关规定”，参考《唢规》8.0.9：“干式系统的配水管道充水时间，不宜大于1min；预作用系统与雨淋系统的配水管道充水时间，不宜大于2min”，故C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]