[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937046":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937046,605,1,"单选题","对火灾报警系统的探测器的设置要求不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","探测区域的每个房间应至少设置一只火灾探测器",false,{"key":16,"text":17,"correct":14},"B","线型光束感烟探测器的设置应保证其接收端避开日光和人工光源直接照射",{"key":19,"text":20,"correct":14},"C","设置线型感温火灾探测器的场所有联动要求时，宜采用两只不同火灾探测器的报警信号组合",{"key":22,"text":23,"correct":24},"D","管路采样式吸气感烟火灾探测器当采样管道采用毛细管布置方式时，毛细管长度不宜超过3m",true,"GB50116-2013 火灾自动报警系统设计规范 6.2.2：“探测区域的每个房间应至少设置一只火灾探测器”，故A正确：选项B，6.2.15：“探测器的设置应保证其接收端避开日光和人工光源直接照射”，故B正确：选项C，6.2.16：“设置线型感温火灾探测器的场所有联动要求时，宜采用两只不同火灾探测器的报警信号组合”，故C正确；选项D，6.2.17：“管路采样式吸气感烟火灾探测器当采样管道采用毛细管布置方式时，毛细管长度不宜超过4m”，故D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]