[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937040":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937040,605,1,"单选题","湿式报警阀组设置时，水力警铃与报警阀连接的管道直径应为（ ）mm，总长度不宜大于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","15，20",false,{"key":16,"text":17,"correct":14},"B","15，25",{"key":19,"text":20,"correct":14},"C","20，15",{"key":22,"text":23,"correct":24},"D","20，20",true,"参考《消规》6.2.8：“水力警铃的工作压力不应小于0.05MPa，并应符合下列规定：1.应设在有人值班的地点附近；2.与报警阀连接的管道，其管径为20mm，总长不宜大于20m”，故D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]