[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937001":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937001,605,1,"单选题","对于A类火灾场所，采用局部应用系统的泡沫灭火系统，则系统设计应符合（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","四周不完全封闭的A类火灾场所，可采用局部应用系统",true,{"key":16,"text":17,"correct":18},"B","覆盖保护对象的时间不应小于2min",false,{"key":20,"text":21,"correct":18},"C","覆盖保护对象最高点的厚度不应大于0.6m",{"key":23,"text":24,"correct":18},"D","泡沫混合液连续供给时间不应大于12min","GB50151-2010泡沫灭火系统设计规范 5.1.2：“局部应用系统可用于下列场所：四周不完全封闭的A类火灾场所：”故A正确：选项B、D，5.1.5：“对于A类火灾场所，局部应用系统的设计应符合下列规定：1覆盖保护对象的时间不应大于2min；故B错误：2覆盖保护对象最高点的厚度宜由试验确定，也可按本规范第6.3.3.1款的规定执行；3泡沫混合液连续供给时间不应小于12min”，故D错误：选项C，6.3.3：“当用于扑救A类火灾或B类火灾时，泡沫供给速率应符合下列规定：1覆盖A类火灾保护对像最高点的厚度不座小于0.6m：”故C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]