[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936988":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936988,605,1,"单选题","按照《泡沫灭火剂》（GB 15308—2006）和《泡沫灭火系统设计规范》（GB 50151—2010）的要求，下列泡沫灭火系统泡沫液需要送检的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","6％型低倍数泡沫液设计用量大于或等于7．0t",true,{"key":16,"text":17,"correct":18},"B","3％型低倍数泡沫液设计用量小于3．5t",false,{"key":20,"text":21,"correct":18},"C","6％蛋白型中倍数泡沫液最小储备量小于2．5t",{"key":23,"text":24,"correct":18},"D","6％合成型中倍数泡沫液最小储备量小于2．0t","按照《泡沫灭火剂》（GB 15308—2006）和《泡沫灭火系统设计规范》（GB50151—2010）的要求，对属于下列情况之一的泡沫液需要送检： ①6％型低倍数泡沫液设计用量大于或等于7．0t； ②3％型低倍数泡沫液设计用量大于或等于3．5t； ③6％蛋白型中倍数泡沫液最小储备量大于或等于2．5t； ④6％合成型中倍数泡沫液最小储备量大于或等于2．0t； ⑤高倍数泡沫液最小储备量大于或等于1．0t； ⑥合同文件规定的需要现场取样送检的泡沫液。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]