[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936972":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936972,605,2,"多选题","变、配电站（室）的设置正确的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","距甲、乙类厂房库房不应小于20m",false,{"key":16,"text":17,"correct":18},"B","距其他建筑物不应小于10m",true,{"key":20,"text":21,"correct":14},"C","距液化石油气罐不应小于25m",{"key":23,"text":24,"correct":18},"D","石油化工装置的变、配电室还应布置在装置的一侧，并位于爆炸危险区范围以外",{"key":26,"text":27,"correct":18},"E","距堆场、可燃液体储罐不应小于25m","BDE","本题考查的是防火防爆的检查。室外变、配电装置距堆场、可燃液体储罐和甲、乙类厂房库房不应小于25m；距其他建筑物不应小于10m；距液化石油气罐不应小于35m；石油化工装置的变、配电室还应布置在装置的一侧，并位于爆炸危险区范围以外。变压器油量越大，建筑物耐火等级越低及危险物品储量越大者，所要求的间距也越大，必要时可加防火墙。故此题答案选B、D、E。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]