[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936957":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936957,605,1,"单选题","某公共建筑和总建筑面积大于20000m2的地下、半地下建筑，其消防应急照明备用电源的连续供电时间不应低于（ ）min。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","90",false,{"key":16,"text":17,"correct":14},"B","20",{"key":19,"text":20,"correct":14},"C","30",{"key":22,"text":23,"correct":24},"D","60",true,"参考《建筑设计防火规范》10.1.5：“建筑内消防座急照明和灯光疏散指示标志的备用电源的连续供电时间应符合下列规定：1建筑高度大于1OOm的民用建筑，不应小于1.5h;2医疗建筑、老年人建筑、总建筑面积大于1OOOOOm2的公共建筑和总建筑面积大于20000m2的地下、半地下建筑，不应少于1.Oh；故D正确。3其他建筑，不应少于0.5h”，",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]