[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936945":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936945,605,1,"单选题","下列关于泡沫比例混合器安装要求的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","泡沫比例混合器（装置）的标注方向应与液流方向一致",true,{"key":16,"text":17,"correct":18},"B","备用的环泵式比例混合器应串联安装在系统上，并应有明显的标志",false,{"key":20,"text":21,"correct":18},"C","管线式比例混合器应安装在压力水的水平管道上并应远离储罐或防护区",{"key":23,"text":24,"correct":18},"D","压力式比例混合装置应分体安装，并应与基础牢固固定","根据《泡沫灭火系统施工及验收规范》GB 50281—20065．4．1—1，泡沫比例混合器（装置）的标注方向应与液流方向一致，A选项正确；根据5．4．2—2，备用的环泵式比例混合器应并联安装在系统上，并应有明显的标志，B选项错误；根据5．4．5，管线式比例混合器应安装在压力水的水平管道上或串接在消防水带上，并应靠近储罐或防护区，其吸液口与泡沫液储罐或泡沫液桶最低液面的高度不得大于1．0m，C选项错误；根据5．4．3，压力式比例混合装置应整体安装，并应与基础牢固固定，D选项错误。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]