[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936935":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936935,605,1,"单选题","下列关于气体灭火系统组件安装要求的说法，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","气动驱动装置的竖直管道应在其始端和终端设防晃支架或采用管卡固定",false,{"key":16,"text":17,"correct":14},"B","气动驱动装置的水平管道应采用管卡固定，管卡的间距不宜大于0.6m",{"key":19,"text":20,"correct":14},"C","气动驱动装置的管道安装后应做气压严密性试验，并合格",{"key":22,"text":23,"correct":24},"D","安装以重力式机械驱动装置时，应保证重物在下落行程中无阻挡，其下落行程应保证驱动所需距离，且不得小于20mm",true,"2020新教材P265 气动驱动装置的竖直管道应在其始端和终端设防晃支架或采用管卡固定，A选项正确；根据5.4.5-3，气动驱动装置的水平管道应采用管卡固定。管卡的间距不宜大于0.6m。转弯处应增设1个管卡，B选项正确；根据5.4.6，气动驱动装置的管道安装后应做气压严密性试验，并合格，C选项正确；根据5.4.2，安装以重力式机械驱动装置时，应保证重物在下落行程中无阻挡，其下落行程应保证驱动所需距离，且不得小于25mm，D选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]