[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936930":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936930,605,1,"单选题","下列关于干粉灭火系统管道气压强度试验的说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","气压强度试验压力取1.5倍系统最大工作压力",true,{"key":16,"text":17,"correct":18},"B","气压试验前，应用加压介质进行预试验，预试验压力为0.2MPa",false,{"key":20,"text":21,"correct":18},"C","当水压强度试验条件不具备时，可采用气压强度试验代替",{"key":23,"text":24,"correct":18},"D","试验时，逐步缓慢增加压力，当压力升至试验压力的50%时，如未发现异状或泄漏，继续按试验压力的10%逐级升压，每级稳压3min，直至达到试验压力","2020新教材P318 当水压强度试验条件不具备时，可采用气压强度试验代替。气压强度试验压力取1.15倍系统最大工作压力。在试验前，用加压介质进行预试验，预试验压力为0.2MPa;试验时，逐步缓慢增加压力，当压力升至试验压力的50%时，如未发现异状或泄漏，继续按试验压力的10%逐级升压，每级稳压3min，直至达到试验压力；保压检查管道各处无变形，无泄漏为合格。气压试验可采用试压装置进行试验，目测观察管网外观和测压用压力表。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]