[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936924":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936924,605,1,"单选题","下列关于火灾自动报警系统的布线的说法中，不符合现行国家消防技术标准的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","火灾自动报警系统的线路应单独布置",false,{"key":16,"text":17,"correct":14},"B","导线在管内或线槽内不应有接头或扭结",{"key":19,"text":20,"correct":21},"C","吊装线槽或管路的吊杆直径不应小于5mm",true,{"key":23,"text":24,"correct":14},"D","每个回路导线对地的绝缘电阻值不应小于20MΩ","《火灾自动报警系统施工及验收规范》（GB 50166-2007），3.2.10，吊装线槽或管路的吊杆直径不应小于6mm。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]