[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936917":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936917,605,2,"多选题","下列关于干粉灭火系统试压的说法中，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","水压强度试验时，其测试点选择在系统管网的最高点",false,{"key":16,"text":17,"correct":14},"B","水压强度试验条件不具备时，可采用气密性试验代替",{"key":19,"text":20,"correct":21},"C","系统水压强度试验和严密性试验采用清水作为介质",true,{"key":23,"text":24,"correct":21},"D","水压强度试验压力为1．5倍系统最大工作压力",{"key":26,"text":27,"correct":21},"E","气压试验可采用试压装置进行试验，目测观察管网外观和测压用压力表","CDE","水压强度试验时，其测试点选择在系统管网的最低点，A选项错误； 系统强度试验和严密性试验采用清水作为介质，当不具备水压强度试验条件时，可采用气压强度试验代替，B选项错误，C选项正确； 水压强度试验压力为1．5倍系统最大工作压力，D选项正确； 气压试验可采用试压装置进行试验，目测观察管网外观和测压用压力表，E选项正确。本题答案为CDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]