[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936910":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936910,605,1,"单选题","下列关于自动喷水灭火系统周期性维护的说法中，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每天应检查储水设备的房间室温",true,{"key":16,"text":17,"correct":18},"B","每天应对水源控制阀、报警阀组进行外观检查，并应保证系统处于无故障状态",false,{"key":20,"text":21,"correct":18},"C","每月检查系统上所有的控制阀门均应采用铅封或锁链固定在开启或规定的状态",{"key":23,"text":24,"correct":18},"D","每月检查消防水池不被他用的技术措施","根据《自动喷水灭火系统施工及验收规范》GB 50084—2017附录G，寒冷季节每天检查储水设备的房间室温。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]