[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936909":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936909,605,2,"多选题","某消防工程施工单位对消火栓系统进行施工前的检查，对消火栓固定接口密封性做现场试验时，根据现行国家标准《消防给水及消防栓系统技术规范》GB 50974—2014规定，下列说法正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","试验数量宜从每批中抽查1％，但不应少于5个",true,{"key":16,"text":17,"correct":18},"B","当仅有1个不合格时，应再抽查2％，但不应少于5个",false,{"key":20,"text":21,"correct":18},"C","应缓慢而均匀地升压2．4MPa，应保压2min",{"key":23,"text":24,"correct":14},"D","当第2次抽查仍有不合格时，不应使用该批消火栓",{"key":26,"text":27,"correct":18},"E","需反复进行5次","AD","根据《消防给水及消火栓系统技术规范》GB 50974—201412．2．3—14，消火栓固定接口应进行密封性能试验，应以无渗漏、无损伤为合格。试验数量宜从每批中抽查1％，但不应少于5个，应缓慢而均匀地升压1．6MPa，应保压2min，当两个及两个以上不合格时，不应使用该批消火栓，当仅有1个不合格时，应再抽查2％，但不应少于10个，并应重新进行密封性能试验；当仍有不合格时，亦不应使用该批消火栓。本题答案为AD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]