[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936907":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936907,605,2,"多选题","根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于自动喷水灭火系统试压和冲洗的要求中，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","管网冲洗应在试压合格后分段进行，冲洗顺序应先地下，后地上，先室内，后室外",false,{"key":16,"text":17,"correct":18},"B","强度试验和严密性试验宜用水进行",true,{"key":20,"text":21,"correct":14},"C","干式自动喷水灭火系统、预作用喷水灭火系统应做水压试验或气压试验",{"key":23,"text":24,"correct":18},"D","管网安装完毕后，必须对其进行强度试验、严密性试验和冲洗",{"key":26,"text":27,"correct":14},"E","管网冲洗应在试压合格后分段进行，室内部分的冲洗应按配水管、配水支管、配水干管的顺序进行","BD","根据《自动喷水灭火系统施工及验收规范》GB 50261—20176．1．4，管网冲洗应在试压合格后分段进行。冲洗顺序应先室外，后室内；先地下，后地上，室内部分的冲洗应按配水干管、配水管、配水支管的顺序进行，AE选项错误；根据6．1．2，强度试验和严密性试验宜用水进行，干式喷水灭火系统、预作用喷水灭火系统应做水压试验和气压试验，B选项正确，C选项错误；根据6．1．1，管网安装完毕后，必须对其进行强度试验、严密性试验和冲洗，D选项正确。本题答案为BD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]