[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936897":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936897,605,2,"多选题","在对火灾自动报警及消防联动控制系统进行验收前检测时，下列组件的抽检数量正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","火灾报警控制器共计2台，抽检2台",true,{"key":16,"text":17,"correct":14},"B","火灾探测器器共计3800只，抽检每个回路的10%～20%",{"key":19,"text":20,"correct":21},"C","区域显示器共计65台，抽检5台",false,{"key":23,"text":24,"correct":14},"D","电动防火门共计30樘，抽检6樘",{"key":26,"text":27,"correct":21},"E","自动喷水灭火系统上的水流指示器共计70只，抽检20只","ABD","火灾报警控制器（含可燃气体报警控制器）和消防联动控制器应按实际安装数量全部进行功能检验。区域显示器，实际安装数量超过10台者，按实际安装数量30%～50%的比例、但不少于5台进行抽检，A选项正确，C选项错误；根据5.1.5 -3 -2，火灾探测器（含可燃气体探测器）和手动火灾报警按钮，实际安装数量超过100只的，按每个回路实际安装数量的10%～20%，但抽验总数不少于20只的比例进行模拟火灾响应（可燃气体报警）和故障信号检验，B选项正确；根据5.1.5 -7，电动防火门、防火卷帘，5樘以下的应全部检验，超过5樘的应按实际安装数量的20%，但不小于5樘的比例抽验联动控制功能，D选项正确；根据5.1.5 -5 -2，自动喷水灭火系统的水流指示器、信号阀等按实际安装数量的30%～50%的比例进行抽验，E选项错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]