[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936894":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936894,605,2,"多选题","雨淋系统的联动控制设计时，联动控制方式，应由（ ）报警信号，作为雨淋阀组开启的联动触发信号。应由消防联动控制器控制雨淋阀组的开启",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","同一报警区域内两只及以上独立的感温火灾探测器",true,{"key":16,"text":17,"correct":18},"B","同一报警区域内两只及以上独立的感烟火灾探测器",false,{"key":20,"text":21,"correct":18},"C","一只感烟火灾探测器与一只手动火灾报警按钮",{"key":23,"text":24,"correct":14},"D","一只感温火灾探测器与一只手动火灾报警按钮",{"key":26,"text":27,"correct":18},"E","同一报警区域内两只及以上独立的手动火灾报警按钮","AD","GB50116-2013 火灾自动报警系统设计规范 4.2.3：“雨淋系统的联动控制设计，应符合下列规定：1联动控制方式，应由同一报警区域内两只及以上独立的感温火灾探测器或一只感温火灾探测器与一只手动火灾报警按钮的报警信号，作为雨淋阀组开启的联动触发信号。座由消防联动控制器控制雨淋阀组的开启”，故A、D正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]