[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936891":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936891,605,2,"多选题","用于消防电梯火灾时，消防备用电源持续运行时间应大于消防水泵、水幕泵火灾时的持续运行时间；下列（ ）需要消防备用电源持续时间大于60min。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","建筑高度大于100米的民用建筑加压风机",true,{"key":16,"text":17,"correct":14},"B","医疗建筑",{"key":19,"text":20,"correct":14},"C","老年人建筑",{"key":22,"text":23,"correct":24},"D","幼儿园",false,{"key":26,"text":27,"correct":14},"E","总建筑面积大于100000m2的公共建筑","ABCE","消防备用电源应满足火灾时消防设备持续运行时间的要求：用于消防电梯火灾时，持续运行时间应大于消防水泵、水幕泵火灾时的持续运行时间：建筑高度大于100m的民用建筑，加压风机、防排烟风机火灾时持续运行时间要大于90min;医疗建筑、老年人建筑、总建筑面积大于100000m2的公共建筑，火灾时持续运行时间要大于60min;其他建筑要大于30min。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]