[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936879":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936879,605,1,"单选题","消防应急标志灯具低位安装在疏散走道及其转角处时，应安装在距地面（ ）m以下的墙上，标志表面应与墙面平行，凸出墙面的部分不应有尖锐角及伸出的固定件。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.5",false,{"key":16,"text":17,"correct":18},"B","1.0",true,{"key":20,"text":21,"correct":14},"C","1.5",{"key":23,"text":24,"correct":14},"D","2.0","GB50016-2014 建筑设计防火规范 10.3.5公共建筑、建筑高度大于54m的住宅建筑、高层厂房（库房）和甲、乙、丙类单、多层厂房，应设置灯光疏散指示标志，并应符合下列规定： 1 应设置在安全出口和人员密集的场所的疏散门的正上方。 2 应设置在疏散走道及其转角处距地面高度1.0m以下的墙面或地面上。灯光疏散指示标志的间距不应大于20m；对于袋形走道，不应大于10m；在走道转角区，不应大于1.0m。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]