[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936876":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936876,605,2,"多选题","下列自动喷水灭火系统组件与设施的连接管中，管径不应小于DN25的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","与DN15直立型喷头连接的短立管",true,{"key":16,"text":17,"correct":14},"B","与DN15下垂型喷头连接的短立管",{"key":19,"text":20,"correct":14},"C","末端试水装置的连接管",{"key":22,"text":23,"correct":24},"D","水力警铃与报警阀间的连接管",false,{"key":26,"text":27,"correct":24},"E","干式系统、预作用系统的供气管道","ABC","选项A、B、C，参考《喷规》8.0.8：“短立管及末端试水装置的连接管，其管径不应小于25㎜”，故A、B、C均正确；选项D，参考《喷规》6.2.8.2：“与报警阀连接的管道其管径应为20㎜”，故D错误；选项E，参考《喷规》8.0.10：“干式系统、预作用系统的供气管道，采用钢管时，管径不宜小于15mm；采用铜管时，管径不宜小于10mm”，故E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]