[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936874":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936874,605,1,"单选题","下列有关火灾自动报警系统布线的做法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","从接线盒引到探测器底座盒的线路，加金属软管保护",false,{"key":16,"text":17,"correct":18},"B","在建筑抹灰及地面工程结束前完成了管内布线",true,{"key":20,"text":21,"correct":14},"C","导线的接头，在接线盒内焊接",{"key":23,"text":24,"correct":14},"D","金属管子进入接线盒时，线盒外侧套锁母，内侧装护口","从接线盒、线槽等处引到探测器底座、控制设备、扬声器的线路，当采用金属软管保护时，其长度不应大于2m，A选项正确；根据3.2.3，在管内或线槽内的布线，应在建筑抹灰及地面工程结束后进行，管内或线槽内不应有积水及杂物，B选项错误；根据3.2.5，导线在管内或线槽内，不应有接头或扭结。导线的接头，应在接线盒内焊接或用端子连接，C选项正确；根据3.2.9，金属管子入盒，盒外侧应套锁母，内侧应装护口；在吊顶内敷设时，盒的内外侧均应套锁母，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]