[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936865":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936865,605,1,"单选题","下列建筑中，室内采用临时高压消防给水系统时，必须设置高位消防水箱的建筑是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","建筑面积为5000m2的单层丙类厂房",false,{"key":16,"text":17,"correct":14},"B","建筑面积为40000m2的4层丁类厂房",{"key":19,"text":20,"correct":14},"C","建筑面积为5000m2的2层办公楼",{"key":22,"text":23,"correct":24},"D","建筑面积为30000㎡的3层商业中心",true,"参考《消防给水及消火栓系统技术规范》6.1.9：“室内采用临时高压消防给水系统时，高位消防水箱的设置应符合下列规定；1.高层民用建筑、总建筑面积大于10000㎡且层数超过2层的公共建筑和其他重要建筑，必须设置高位消防水箱”，选项D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]