[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936857":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936857,605,1,"单选题","下列关于自动喷水灭火系统的喷头选择叙述中，（ ）不正确。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不做吊顶的场所可采用直立型喷头",false,{"key":16,"text":17,"correct":18},"B","设有自动喷水系统的房间，其吊顶内必须设喷头",true,{"key":20,"text":21,"correct":14},"C","宾馆客房、办公室可采用边墙型喷头",{"key":23,"text":24,"correct":14},"D","干式系统、预作用系统应采用直立型喷头或干式下垂型喷头","选项A、B，参考《喷规》6.1.3：“湿式系统的喷头选型应符合下列规定：1不做吊顶的场所，当配水支管布置在梁下时，应采用直立型喷头；2吊顶下布置的喷头，应采用下垂型喷头或吊顶型喷头：3顶板为水平面的轻危险级、中危险级Ⅰ级居室和办公室，可采用边墙型喷头：4自动喷水一泡沫联用系统应采用洒水喷头：5易受碰撞的部位，应采用带保护罩的喷头或吊顶型喷头”，故A、C正确；选项B，参考《喷规》7.1.8：“净空高度大于800mm的闷顶和技术夹层内有可燃物时，应设置喷头，不满足该条件的闷顶可不设喷头”。故B错误；选项D，参考《喷规》6.1.4：“干式系统、预作用系统应采用直立型喷头或干式下垂型喷头”，故D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]