[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936850":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936850,605,2,"多选题","下列关于消防配电电线电缆的选择及线路敷设的要求描述中，正确的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","火灾报警与消防联动控制系统的布线要选择铜芯绝缘电线或铜芯电缆",true,{"key":16,"text":17,"correct":14},"B","消防配电线路当采用矿物绝缘类不燃性电缆时，可直接明敷",{"key":19,"text":20,"correct":14},"C","消防配电消防配电干线宜按防火分区划分，消防配电支线不宜穿越防火分区，当跨越防火分区时应采取防止火灾延燃的措施",{"key":22,"text":23,"correct":24},"D","消防配电线路采用矿物绝缘类不燃性电缆时，不能与其他配电线路敷设在同一电缆井、沟内",false,{"key":26,"text":27,"correct":24},"E","配电电线电缆暗敷时，应穿管并应敷设在不燃性结构内且保护层厚度不应小于50mm","ABC","参考《建筑设计防火规范》10.1.10选项A，火灾报警与消防联动控制系统的布线要选择铜芯绝缘电线或铜芯电缆。故A正确。选项B，火灾报警与消防联动控制系统的布线要选择铜芯绝缘电线或铜芯电缆。故B正确。选项C，消防配电消防配电干线宜按防火分区划分，消防配电支线不宜穿越防火分区，当跨越防火分区时应采取防止火灾延燃的措施。故C正确。选项D，消防配电线路宜与其他配电线路分开敷设在不同的电缆井、沟内：确有困难需敷设在同一电缆井、沟内时，应分别布置在电缆井、沟的两侧，且消防配电线路应采用矿物绝缘类不燃性电缆。故D错误可知，A、B、C正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]