[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936846":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936846,605,1,"单选题","下列关于屋顶消防水箱的设置要求中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","安装无管道的侧面，净距0.8m",false,{"key":16,"text":17,"correct":14},"B","设有人孔的水箱顶面与建筑物本体板底的净空高度为0.8m",{"key":19,"text":20,"correct":14},"C","管道外壁与建筑本体墙面之间的通道宽度为0.8m",{"key":22,"text":23,"correct":24},"D","进水管充满水箱有效体积的时间为12h",true,"参考《消防给水及消火栓系统技术规范》5.2.6：高位消防水箱应符合下列规定：4.高位消防水箱外壁与建筑本体结构墙面或其他池壁之间的净距，应满足施工或装配的需要，无管道的侧面，净距不宜小于0.7m;安装有管道的侧面，净距不宜小于1.0m，且管道外壁与建筑本体墙面之间的通道宽度不宜小于0.6m，设有人孔的水箱顶，其顶面与其上面的建筑物本体板底的净空不应小于0.8m。选项A，安装无管道的侧面，净距0.8m＞0.7m，故A正确。选项B，设有人孔的池顶，顶板面与上面建筑本体板底的净空≥0.8m，故B正确。选项C，管道外壁与建筑本体墙面之间的通道宽度为0.8m＞0.6m，故C正确。选项D，参考《消防给水及消火栓系统技术规范》5.7.6：进水管的管径应满足消防水箱8h充满水的要求，但管径不应小于DN32，进水管宜设置液位阀或浮球阀。故D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]