[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936835":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936835,605,1,"单选题","下列关于室内消火栓给水系统的叙述中，（ ）是错误的。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","室内消火栓给水应与自动喷水灭火系统分开设置，特殊情况下可合用消防泵",false,{"key":16,"text":17,"correct":14},"B","高层民用建筑的室内消防给水系统，应与生活给水系统分开独立设置",{"key":19,"text":20,"correct":14},"C","室内消防给水管道、消防水池与室外生活给水管或生活一消防合用管道连接时，应采取防止回流污染的技术措施",{"key":22,"text":23,"correct":24},"D","高层厂房室内消防给水系统在满足条件时可与生产给水系统合用",true,"参考《消防给水及消火栓系统技术规范》6.1.8：“室内应采用高压或临时高压消防给水系统，且不应与生产生活给水系统合用”，高层厂房消火栓栓口动压应大于0.35MPa，一般市政水压不能满足要求，一般情况下均采用临时高压消防给水系统，故D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]