[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936818":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936818,605,2,"多选题","下列关于机械加压送风系统的说法正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防烟楼梯间宜每隔4-5层设置一个加压送风口",false,{"key":16,"text":17,"correct":18},"B","前室或合用前室只能选用常闭式加压送风口",true,{"key":20,"text":21,"correct":14},"C","闭式加压送风口设手动或电动可开启装置，且手动开启装置的高度距地面1.3-1.5m",{"key":23,"text":24,"correct":18},"D","机械加压送风机与排烟风机设置在同一平面时，其水平距离不应小于1Om",{"key":26,"text":27,"correct":18},"E","封闭的避难层应设独立的机械加压送风系统","BDE","选项A，楼梯间每隔2-3层设一个加压送风口，前室、合用前室每层设一个常闭式加压送风口，故A错误： 选项B、C.加压送风口的类型有两种：常开式（只能用于楼梯间）、常闭式（用于楼梯间、前室、合用前室）：常闭式加压送风口必须设手动和电动可开启装置，且手动开启装置的高度距地面1.3-1.5m，故B正确，C错误； 选项D,机械加压送风机与排烟风机上下设置时，上排下进，高差3m（住宅层高）：设置在同一平面时，其水平距离不应小于1Om，故D正确： 选项E，封闭的避难层应设独立的机械加压送风系统，注意：避难层是否采用可以采用自然通风与建筑高度和类型无关，只与是否能够满足可开启外窗有关，故E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]