[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936813":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936813,605,1,"单选题","下列关于干式自动喷水灭火系统的说法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","在准工作状态下，由稳压系统维持干式报警阀入口前管道内的充水压力",false,{"key":16,"text":17,"correct":14},"B","在准工作状态下，干式报警阀出口后的配水管道内应充满有压气体",{"key":19,"text":20,"correct":21},"C","当发生火灾后，干式报警阀开启，压力开关动作后管网开始排气充水",true,{"key":23,"text":24,"correct":14},"D","当发生火灾后，配水管道排气充水后，开启的喷头开始喷水","干式系统，发生火灾后，喷头爆破进行排气，管网气压降低，加速器开启排气，阀瓣在压力差的作用下打开，水通过阀瓣进入管网，同时流到压力开关处触发压力开关动作，故C错误，先排气充水.才触发压力开关动作。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]