[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936804":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936804,605,1,"单选题","下列对供水设施的维护管理中，说法正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","每日应手动启动消防水泵运转一次，并应检查供电电源的情况",false,{"key":16,"text":17,"correct":14},"B","每年对气压水罐的压力和有效容积进行检测一次",{"key":19,"text":20,"correct":14},"C","每周应模拟消防水泵自动控制的条件自动启动消防水泵运转一次，且应自动记录自动巡检情况，每周应检测记录",{"key":22,"text":23,"correct":24},"D","每季度应对消防水泵的出流量和压力进行一次试验",true,"参考《消防给水及消火栓系统技术规范》14.0.4：“消防水泵和稳压泵等供水设施的维护管理应符合下列规定：1.每月应手功启动消防水泵运转一次，并应检查供电电源的情况；故A错误；2.每周应模拟消防水泵自动控制的条件自动启动消防水泵运转一次。且应自动记录自动巡检情况，每月应检测记录：C选项“每周应检测记录”错误，应为“每月应捡测记录”，故C错误；5.每季度应对消防水泵的出流量和压力进行一次试验：故D正确；6.每月应对气压水罐的压力和有效容积等进行一次检测”，故B错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]