[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936798":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936798,605,2,"多选题","下列场所的备用照明，应能保证正常照度的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","首层消防控制室",true,{"key":16,"text":17,"correct":18},"B","生活水泵房",false,{"key":20,"text":21,"correct":14},"C","通信机房",{"key":23,"text":24,"correct":14},"D","地下室发电机房",{"key":26,"text":27,"correct":14},"E","防排烟机房","ACDE","参考《建规》10.3.3，消防控制室、消防水泵房、自备发电就房、配电室、防排烟机房以及发生火灾时仍需正常工作的消防设备房应设置备用照明，其作业面的最低照度不应低于正常照明的照度。故A、C、D、E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]