[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936794":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936794,605,1,"单选题","下列（ ）可以不设置疏散照明系统。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","消防电梯间前室",false,{"key":16,"text":17,"correct":14},"B","展览厅",{"key":19,"text":20,"correct":21},"C","层高4m的6层住宅楼",true,{"key":23,"text":24,"correct":14},"D","商场疏散走道","参考《建筑设计防火规范》10.3.1：除建筑高度小于27m的住宅建筑外，民用建筑、厂房和丙类仓库的下列部位应设置疏散照明：1.封闭楼梯间、防烟楼梯间及其前室、消防电梯间的前室或合用前室、避难走道、避难层（间）：故A正确。2.观众厅、展览厅、多功能厅和建筑面积大于200m2的营业厅、餐厅、演播室等人员密集的场所：故B正确。3.建筑面积大于100m2的地下或半地下公共活动场所：4.公共建筑内的疏散走道：故D正确。5.人员密集的厂房内的生产场所及疏散走道。选项C，6层住宅楼属于建筑高度小于27m的住宅建筑，故不用设置疏散照明。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]