[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936786":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936786,605,2,"多选题","为确定系统设计详见数的实体火灾模拟试验应由国家授权的机构实施。在工程应用中采用实体模拟实验结果时，应符合下列（ ）规定。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","系统设计喷雾强度不应小于试验所用喷雾强度",true,{"key":16,"text":17,"correct":14},"B","喷头最低工作压力不应小于试验测得最不利点喷头的工作压力",{"key":19,"text":20,"correct":21},"C","系统设计流量不应小于试验所用设计流量",false,{"key":23,"text":24,"correct":14},"D","喷头布置间距和安装高度分别不应大于试验时的喷头间距和安装高度",{"key":26,"text":27,"correct":14},"E","喷头的安装角度应与试验安装角度一致","ABDE","参考《细水雾规范》3.4.10：“为确定系统设计参考数的实体火灾模拟试验应由国家授权的机构实施，并应符合本规范附录A的规定。在工程应用中采用实体模拟实验结果时，应符合下列规定：1.系统设计喷雾强度不应小于试验所用喷雾强度；故A正确。2.喷头最低工作压力不应小于试验测得最不利点喷头的工作压力；故B正确。3.喷头布置间距和安装高度分别不应大于试验时的喷头间距和安装高度：故D正确。4.喷头的安装角度应与试验安装角度一致。故E正确。系统设计流量与试验设计流量的关系，规范没有给出明确规定，故C错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]