[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936778":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936778,605,2,"多选题","室内消火栓检测验收时应符合（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","室内消火栓的选型、规格应符合设计要求",true,{"key":16,"text":17,"correct":18},"B","同一建筑物内设置的消火栓应采用统一规格的消火栓箱",false,{"key":20,"text":21,"correct":14},"C","试验用消火栓栓口处应设置压力表",{"key":23,"text":24,"correct":18},"D","室内消火栓处应设置直接启动消防水泵的按钮",{"key":26,"text":27,"correct":14},"E","室内消火栓应设置明显的永久性固定标志","ACE","参考《消防给水及消火栓系统技术规范》12.3.9：室内消火栓及消防软管卷盘或轻便水龙的安装应符合下列规定：1.室内消火拴及消防软管卷盘和轻便水龙的选型、规格应符合设计要求：故A正确。2.同一建筑物内设置的消火栓、消防软管卷盘和轻便水龙应采用统一规格的栓口、消防水枪和水带及配件：故B错误。3.试验用消火栓栓口处应设置压力表；故C正确。4.当消火栓设置减压装置时，应检查减压装置符合设计要求，且安装时应有防止砂石等杂物进入一栓口的措施：5.室内消火栓及消防软管卷盘和轻便水龙应设置明显的永久性固定标志，当室内消火栓因美观要求需要隐蔽安装时，应有明显的标志，并应便于开启使用：故E正确。参考《消防给水及消火栓系统技术规范》11.0.19：消火栓按钮不宜作为直接启动消防水泵的开关，但可作为发出报警信号的开关或启动干式消火栓系统的快速启闭装置等。故D错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]