[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936776":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936776,605,1,"单选题","设置消防水泵时应设置备用泵，但当建筑高度为50米的住宅的室外消防用水量小于或者等于（ ）L\u002Fs时，可不设置备用泵。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","15",{"key":19,"text":20,"correct":14},"C","20",{"key":22,"text":23,"correct":24},"D","25",true,"参考《消防给水及消火栓系统技术规范》5.1.10：“消防水泵应设置备用泵，其性能应与工作泵性能一致，但下列建筑除外：1.建筑高度小于54m的住宅和室外消防给水设计流量小于等于25L\u002Fs的建筑；2.室内消防给水设计流量小于等于10L\u002Fs的建筑”，故D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]