[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936772":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936772,605,1,"单选题","泡沫一水喷淋系统与泡沫喷雾系统是泡沫系统常见的应用形式，下列关于泡沫一水喷淋与泡沫喷雾系统的描述中正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","泡沫—水喷琳系统泡沫混合液连续供给时间不应小于5min",false,{"key":16,"text":17,"correct":14},"B","泡沫—水喷琳系统泡沫混合液与水的连续供给时间之和不应小于30min",{"key":19,"text":20,"correct":21},"C","泡沫一水预作用系统与泡沫一水干式系统的管道充水时间不宜大于1min",true,{"key":23,"text":24,"correct":14},"D","泡沫一喷雾系统当保护油浸电力变压器时，泡沫混合液或泡沫预混液连续供给时间不应小于10min","GB 50151-2010 泡沫灭火系统设计规范 7.1.3：“泡沫一水喷琳系统泡沫混合液与水的连续供给时间，应符合下列规定：1泡沫混合液连续供给时间不应小于10min；故A错误：2泡沫混合液与水的连续供给时间之和不应小于60min”，故B错误；选项C，7.3.10：泡沫一水预作用系统与泡沫一水干式系统的管道充水时间不宜大于1min。故C正确；选项D，7.4.2：泡沫一喷雾系统当保护油浸电力变压器时，泡沫混合液或泡沫预混液连续供给时间不应小于15min，故D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]