[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936764":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936764,605,2,"多选题","某项目室内消防给水系统采用镀锌钢管，水泵扬程为1.0MPa，系统工作压力为1.32MPa，下列关于管网试压和冲洗的说法中，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","水压强度试验压力为1.72MPa",true,{"key":16,"text":17,"correct":18},"B","水压强度试验的测试点设在最不利消火栓处，管网注水排气时，缓慢升压达到0.35MPa压力后稳压30min，管网无泄漏、无变形，且压力降≤0.05MPa",false,{"key":20,"text":21,"correct":14},"C","管网冲洗在水压强度试验后，按供水干管、水平管和立管的顺序进行",{"key":23,"text":24,"correct":14},"D","水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为系统工作压力，稳压24h，应无泄漏",{"key":26,"text":27,"correct":14},"E","气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.01MPa","ACDE","选项A，参考《消防给水及消火栓系统技术规范》12.4.2：“压力管道水压强度试验的试验压力应符合表12.4.2的规定”， 表12.4.2压力管道水压强度试验的试验压力， 故A正确，水压强度试验压力为1.32+0.4=1.72MPa；选项B，参考《消防给水及消火栓系统技术规范》12.4.3：“水压强度试验的测试点应设在系统管网的最低点。对管网注水时，应将管网内的空气排净，并应缓慢升压，达到试验压力后，稳压30min后，管网应无泄漏、无变形，且压力降不应大于0.05MPa”，故B错误，测试点错误，压力也错误：选项C，参考《消防给水及消火栓系统技术规范》12.4.1：“消防给水及消火栓系统试压和冲洗应符合下列要求：4管网冲洗应在试压合格后分段进行。冲洗顺序应先室外，后室内；先地下，后地上；室内部分的冲洗应按供水干管、水平管和立管的顺序进行；”故C正确；选项D，参考《消防给水及消火栓系统技术规范》12.4.4：“水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为系统工作压力，稳压24h，应无泄漏”，故D正确；选项E，参考《消防给水及消火栓系统技术规范》12.4.7：“气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.01MPa”，故E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]