[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936760":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936760,605,1,"单选题","某数据处理控制中心设有七氟丙烷气体灭火系统，系统启动灭火时，防护区实际使用浓度不应大于下列（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","灭火设计浓度",false,{"key":16,"text":17,"correct":18},"B","有毒性反应浓度",true,{"key":20,"text":21,"correct":14},"C","惰化设计浓度",{"key":23,"text":24,"correct":14},"D","无毒性反应浓度","参考《气体灭火规范》6.0.7：“有人工作防护区的灭火设计浓度或实际使用浓度，不应大于有毒性反应浓度（LOAEL浓度），该值应符合本规范附录G的规定”。数据处理控制中心属于有人工作的防护区，因此B正确。另此题可以假设有一个灭火浓度，然后设计浓度是灭火浓度的1.3倍，实际浓度不应大于设计浓度的1.1倍；有爆炸危险的防护区采用惰化设计浓度，数据中心无爆炸危险，因此排除灭火设计浓度、惰化设计浓度。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]