[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936757":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936757,605,1,"单选题","某库房设有室内消火栓给水系统，则其消火栓水枪的充实水柱长度不应小于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","7m",false,{"key":16,"text":17,"correct":18},"B","13m",true,{"key":20,"text":21,"correct":14},"C","10m",{"key":23,"text":24,"correct":14},"D","8m","参考《消防给水及消火栓系统技术规范》7.4.12：室内消火栓栓口压力和消防水枪充实水柱，应符合下列规定：2.高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0.35MPa，且消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0.25MPa，且消防水枪充实水柱应按10m计算。故选B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]