[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936753":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936753,605,1,"单选题","某建筑内走道宽度2.0米，在内走道顶棚上居中安装安装探测器时，点型感温探测器的安装间距不应超过（ ）米，点型感烟探测器的安装间距不应超过（ ）米。探测器距墙的距离不应大于安装距离的一半。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10，15",true,{"key":16,"text":17,"correct":18},"B","15，10",false,{"key":20,"text":21,"correct":18},"C","15，20",{"key":23,"text":24,"correct":18},"D","20，15","GB50116-2013 火灾自动报警系统设计规范 6.2.4：“在宽度小于3m的内走道顶棚上设置点型探测器时，宜居中布置。感温火灾探测器的安装间距不应超过10m；感烟火灾探测器的安装间距不应超过15m,；探测器至端墙的距离，不应大于探测器安装间距的1\u002F2”，故A正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]