[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936746":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936746,605,1,"单选题","某高层宾馆，下列关于消防设备配电装置的做法中，不能满足消防设备供电要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","引至消防泵的两路电源在泵房内末端自动切换",false,{"key":16,"text":17,"correct":14},"B","消防负荷的配电线路设置短路动作保护装置",{"key":19,"text":20,"correct":21},"C","消防负荷的配电线路设置过负荷和过、欠电压保护装置",true,{"key":23,"text":24,"correct":14},"D","消防负荷的配电线路未设置剩余电流保护装置","参考《火灾自动报警系统设计规范》10.1.4：“火灾自动报警系统主电源不应设置剩余电流动作保护和过负荷保护装置”，条文说明：剩余电流动作保护和过负荷保护装置一旦报警会自动切断电源，因此火灾自动报警系统主电源不应采用剩余电流动作保护和过负荷保护装置保护。故C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]