[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936740":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936740,605,1,"单选题","某2层地上商店建筑，每层建筑面积为6000m2，所设置的自动喷水灭火系统应至少设置（ ）个水流指示器。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","5","地上2层商店为多层民用建筑.建筑耐火等级不应低于3级，但是若为一、二级，则每个防火分区的最大允许建筑面积更大，即为2500m2。设置自喷后可以为5000m2，即每层至少应划分为2个防火分区。参考《喷规》6.3.1：“6.3.1除报警阀组控制的喷头只保护不超过防火分区面积的同层场所外，每个防火分区、每个楼层均应设水流指示器”，4个防火分区，故至少应没置4个水流指示器，C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]