[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936735":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936735,605,1,"单选题","建筑高度为48m的16层住宅建筑，一梯三户，每户建筑面积120m2，每个单元设置一座防烟楼梯间，一部消防电梯和一部客梯。该建筑每个单元需设置的室内消火栓总数量不应少于（ ）个。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","16",true,{"key":16,"text":17,"correct":18},"B","8",false,{"key":20,"text":21,"correct":18},"C","32",{"key":23,"text":24,"correct":18},"D","48","参考《消防给水及消火栓系统技术规范》7.4.3：“设置室内消火拴的建筑，包括设备层在内的各层均应设置消火拴”，参考《消防给水及消火栓系统技术规范》7.4.6：“室内消火栓的布置应满足同一平面有2支消防水枪的2股充实水柱同时达到任何部位的要求，但建筑高度小于或等于24.0m且体积小于或等于5000m3的多层仓库、建筑高度小于或等于54m且每单元设置一部疏散楼梯的住宅，以及本规范表3.5.2中规定可采用1支消防水枪的场所，可采用1支消防水枪的1股充实水柱到达室内任何部位”，故每层可设1个消火栓，共16层，总数量为16个。A正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]