[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936734":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936734,605,1,"单选题","建筑高度120米的住宅的消防水箱最小有效容积（ ）和最不利点处的静水压力为（ ）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","18m3，0.07MPa",false,{"key":16,"text":17,"correct":14},"B","18m3，0.10MPa",{"key":19,"text":20,"correct":21},"C","36m3，0.07MPa",true,{"key":23,"text":24,"correct":14},"D","36m3，0.10MPa","消防给水及消火栓系统技术规程：5．2．1 临时高压消防给水系统的高位消防水箱的有效容积应满足初期火灾消防用水量的要求，并应符合下列规定： 1 一类高层公共建筑，不应小于36m3，但当建筑高度大于100m时，不应小于50m3，当建筑高度大于150m时，不应小于100m3",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]