[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936725":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936725,605,2,"多选题","管径为DN150mm的消防给水管道架空安装时，应按规定设置防晃支架，下列相关要求中，正确的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","配水管宜在中点设一个防晃支架",true,{"key":16,"text":17,"correct":14},"B","配水干管及配水管，配水支管的长度超过15m，每15m长度内应至少设1个防晃支架",{"key":19,"text":20,"correct":14},"C","管道拐弯、三通及四通位置处应设1个防晃支架",{"key":22,"text":23,"correct":24},"D","架空管道每段管道设置的防晃支架不应少于2个",false,{"key":26,"text":27,"correct":14},"E","立管应在其始端和终端设防晃支架或采用管卡固定","ABCE","选项A、B、C，参考《消防给水及消火栓系统技术规范》12.3.20-6：“下列部位应设置固定支架或防晃支架：1）配水管宜在重点设一个防晃支架，但当管径小于DN50时可不设；故A正确；2）配水干管及配水管，配水支管的长度超过15m，每15m长度内应至少设1个防晃支架，但当管径不大于DN40可不设；故B正确；3）管径大于DN50的管道拐弯、三通及四通位置处应设1个防晃支架；”故C正确；选项D、E，参考《消防给水及消火栓系统技术规范》12.3.21：“架空管道每段管道设置的防晃支架不应少于1个；当管道改变方向时，应增设防晃支架；立管应在其始端和终端设防晃支架或采用管卡固定”，故D错误，E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]