[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936723":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936723,605,1,"单选题","关于水流指示器的设置不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","湿式系统必须设置水流指示器",true,{"key":16,"text":17,"correct":18},"B","设置水流指示器时应按防火分区及楼层设置",false,{"key":20,"text":21,"correct":18},"C","仓库内顶板下喷头与货架内喷头应分别设置水流指示器",{"key":23,"text":24,"correct":18},"D","当水流指示器入口前设置控制阀时，应采用信号阀","选项A、B，参考《喷规》6.3.1：“除报警阀组控制的喷头只保护不超过防火分区面积的同层场所外，每个防火分区、每个楼层均应设水流指示器”，故A错误，B正确；选项C，参考《喷规》6.3.2：“仓库内顶板下喷头与货架内喷头应分别设置水流指示器”，故C正确；选项D，参考《喷规》6.3.3：“当水流指示器入口前设置阀时，应采用信号阀”，故D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]