[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936722":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936722,605,1,"单选题","关于室外消火栓进出口口径检查，错误的设置是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","室外地上式消火栓进水口口径为DN100，出水口口径为一个DN100、两个DN65",false,{"key":16,"text":17,"correct":14},"B","室外地上式消火栓进水口口径为DN150，出水口口径为一个DN150、两个DN65",{"key":19,"text":20,"correct":14},"C","室外地下式消火栓进水口口径为DN100，出水口口径为一个DN100、一个DN65",{"key":22,"text":23,"correct":24},"D","室外地下式消火栓进水口口径为DN150，出水口口径为一个DN150、一个DN65",true,"参考《消防给水及消火栓系统技术规范》7.2.2：“市政消火栓宜采用直径DN150的室外消火栓，并应符合下列要求： 1.室外地上式消火栓应有一个直径为150mm或100mm和两个直径为65mm的栓口；故A、B正确； 2.室外地下式消火栓应有直径为100mm和65mm的栓口各一个”，故C正确，D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]