[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936714":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936714,605,1,"单选题","根据《水喷雾规》GB50219，对水喷雾灭火系统应进行联动试验检查，系统响应时间、工作压力和流量应符合设计要求：当系统为手动控制时，应以手动方式进行至少（ ）检查系统的动作情况及信号反馈情况。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","3次",false,{"key":16,"text":17,"correct":18},"B","1次",true,{"key":20,"text":21,"correct":14},"C","4次",{"key":23,"text":24,"correct":14},"D","5次","参考《水喷雾规》8.4.11-3:“联动试验应符合下列规定：3系统的响应时间、工作压力和流量应符合设计要求。检查数量：全数检查。检查方法：当为手动控制时，以手动方式进行1次~2次试验；当为自动控制时，以自动和手动方式各进行1次~2次试验，并用压力表、流量计、秒表计量”，故B正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]