[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936709":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936709,605,2,"多选题","对于流散B类火灾场所或面积不大于100m的流淌B类火灾场所，一般可能选择以下（ ）形式的泡沫灭火系统。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","全淹没系统",false,{"key":16,"text":17,"correct":18},"B","局部应用系统",true,{"key":20,"text":21,"correct":18},"C","移动式系统",{"key":23,"text":24,"correct":14},"D","固定式系统",{"key":26,"text":27,"correct":14},"E","半固定式系统","BC","GB50151-2010泡沫灭火系统设计规范 5.1.1：“全淹没系统可用于小型封闭空间场所与设有阻止泡沫流失的固定围墙或其他围挡设施的小场所”。5.1.2：“局部应用系统可用于下列场所：1.四周不完全封闭的A类火灾场所：2.限定位置的流散B类火灾场所：3固定位置面积不大于100m2的流淌B类火灾场所”。5.1.3：“移动式系统可用于下列场所：1发生火灾的部位难以确定或人员难以接近的较小火灾场所；2流散的B类火灾场所：3不大于100m2的流淌B类火灾场所”。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]