[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936708":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936708,605,2,"多选题","对于工程项目泡沫液用量较多的情况，需要将其送至具备相应资质的检测单位进行检测。对属于（ ）情况的泡沫液需要送检。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","6%型低倍数泡沫液设计用量大于或等于7.0t",true,{"key":16,"text":17,"correct":18},"B","6%型低倍数泡沫液设计用量大于或等于3.5t",false,{"key":20,"text":21,"correct":18},"C","3%蛋白型中倍数泡沫液最小储备量大于或等于2.5t",{"key":23,"text":24,"correct":14},"D","6%合成型中倍数泡沫液最小储备量大于或等于2.0t",{"key":26,"text":27,"correct":14},"E","高倍数泡沫液最小储备量大于或等于1.0t","ADE","GB50281-2006泡沫灭火系统施工及验收规范 4.2.2：“对属于下列情况之一的泡沫液，应由监理工程师组织现场取样，送至具备相应资质的检测单位进行检测，其结果应符合国家现行有关产品标准和设计要求。6%型低倍数泡沫液设计用量大于或等于7.0t。故A正确；3%型低倍数泡沫液设计用量大于或等于3.5t。故B错误：6%蛋白型中倍数泡沫液最小储备量大于或等于2.5t。故C错误；6%合成型中倍数泡沫液最小储备量大于或等于2.0t。故D正确；高倍数泡沫液最小储备量大于或等于1.0t。故E正确。合成文件规定的需要现场取样送检的泡沫液”，",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]